IMPORTANT• Complete all forms under this appendix for each unit and email, fax or mail to Venmar CES imme-diately after start-up to validate warranty
Serial Number: _____________________________________Table E1: Pre Start-up ChecklistChecklist Item Check √ N/A1 Check the electrical disconnect set to
Table E1: Pre Start-up ChecklistChecklist Item Check √ N/A12Check the heat pipe fins for any fin defects from shipping or installation.a. Remove retain
Table E2: Start-up ChecklistChecklist Item Check √ N/A10Recheck the voltage at the disconnect switch against the nameplate and against phase-to-phase
Start-up Readings• Allow unit to reach steady state before taking readings.• Complete based on options included with unitNameplate voltageInput volt
Serial Number: _____________________________________Table E6: Start-up Readings – CompressorsFull Load Amps (Nameplate Amps)Amp DrawAfter compressor h
Table E7: Start-up Readings – WSHPWaterside Cooling Mode Waterside Heating ModeEntering Temp. (°F/°C)Leaving Temp. (°F/°C)Temp. Difference (°F/°C)Ente
Serial Number: _____________________________________This unit has been checked out and started according with the above procedures and completed forms