1. Complete wire connections between the unit and
the exhaust air damper by matching the correct wire
colors on the actuator and end switch with the wire
colors on the schematic before installing (ACT4004,
if applicable).
2. The supply air temperature sensor (SN3002) is in-
cluded loose in the unit and can be found in the con-
trol panel. Install the temperature sensor a minimum
of 12 feet downstream of the unit. The further the
sensor is from the heating/cooling source, the greater
the accuracy in readings because more air mixing is
allowed. Wire it to IP4 on the DDC (DDC3002). A
coil of wire can be found in the supply fan cabinet
behind the fan (or in the gas cabinet if applicable).
One end of this coil is connected to IP4 on the DDC
(DDC3002).
3. Install the BacStat II (DC3036). It is included loose in
the unit and can be found in the control panel. De-
termine required location and connect to terminals
FW 380, 381, 382 and 383 using two twisted pair
cables, the first for power connection. The LinkNet
Cable needs to be balanced 100 to 120 ohm nomi-
nal impedance Twisted Shielded Pair Cable, Nominal
capacitance of 16PF/FT or lower (see Appendix C for
networking practice).
4. Units will require a dry contact start interlock. See
Stand Alone Operation or Network Operation and
Ventilation Control Scheduling Modes. Determine
required method, mode and terminals and make
connection.
Appendix A: Control Wiring Connections Example