Adjust the following setpoints:
#124 – Enthalpy Free Cooling Setpoint
• Limits: 10–70 Btu/lbs [23–163 Joules/Gram]
• Factory set: 20 Btu/lbs
• BACnet variable: AV45
• Function: The enthalpy free cooling setpoint is the
measured enthalpy that the unit will go into free
cooling.
#125 – Enthalpy Free Cooling Span
• Limits: 5–20 Btu/lbs [11–46 Joules/Gram]
• Factory set: 5 Btu/lbs
• BACnet variable: AV46
• Function: The enthalpy free cooling span is the differ-
ential above and below the free cooling setpoint.
#126 – Enthalpy Free Cooling Reset
• Limits: 0–100%
• Factory set: 50%
• BACnet variable: AV47
• Function: The enthalpy free cooling reset is the per-
centage of the span value under the setpoint.
Differential Enthalpy (On/Off)
If the outside air temperature is above the summer set-
point (selectable) and if the outside air enthalpy is less
than return air enthalpy and in the enthalpy free cooling
setpoint range, the wheel stops.
Adjust the following setpoints:
#124 – Enthalpy Free Cooling Setpoint
• Limits: 10–70 Btu/lbs [23–163 Joules/Gram]
• Factory set: 20 Btu/lbs
• BACnet variable: AV45
• Function: The enthalpy free cooling setpoint is the
measured enthalpy that the unit will go into free
cooling.
#125 – Enthalpy Free Cooling Span
• Limits: 5–20 Btu/lbs [11–46 Joules/Gram]
• Factory set: 5 Btu/lbs
• BACnet variable: AV46
• Function: The enthalpy free cooling span is the differ-
ential above and below the free cooling setpoint.
#126 – Enthalpy Free Cooling Reset
• Limits: 0–100%
• Factory set: 50%
• BACnet variable: AV47
• Function: The enthalpy free cooling reset is the per-
centage of the span value under the setpoint.
Variable Free Cooling (Dry Bulb Setpoint Wheel VFD
Modulation)
If the outside air temperature is above the summer set-
point (selectable) and if the outside air temperature is less
than the return air temperature and less than the supply
air temperature setpoint, the wheel modulates to the
wheel leaving temperature setpoint.
Dx Cooling, WSHP Cooling, One Compressor,
Optional VRC
®
(Discharge Air Temperature
Control)
If the outside air temperature is above the summer set-
point (selectable) and if the coil leaving air temperature
rises above the coil leaving air temperature setpoint (se-
lectable), the first compressor starts. Modulate compressor
to coil leaving air temperature setpoint. Reheat heats up
the supply air to the cooling setpoint (if equipped).
Dx Cooling, WSHP Cooling, Two Compressors,
Single Compressor, Two-stage (Discharge Air
Temperature Control)
If the outside air temperature is above the summer set-
point (selectable) and if the coil leaving air temperature
rises above the coil leaving air setpoint (selectable), the
first compressor starts. If more cooling is needed based
on the coil leaving air temperature setpoint, after staging
delay, the second compressor starts. Reheat heats up the
supply air to the cooling setpoint (if equipped).
Dx Cooling, WSHP Cooling, Two Compressors,
First Compressor VRC (Discharge Air
Temperature Control)
If outside air temperature is above summer setpoint (se-
lectable), and if coil leaving air temperature rises above coil
leaving air setpoint (selectable), first compressor starts and
modulates to maintain setpoint. If more cooling is needed
based on coil leaving air temperature setpoint, after stag-
ing delay, second compressor starts. The first compressor
will continue to modulate to maintain coil leaving air tem-
perature. Reheat heats up supply air to cooling setpoint (if
equipped)
Dx Cooling, WSHP Cooling, One Compressor,
Optional VRC (Room Air Temperature Control)
If the outside air temperature is above the summer set-
point (adjustable) and if the (return) room air temperature
rises above the summer zone setpoint and the coil leaving
air temperature is above the coil leaving setpoint, the first
compressor starts. Compressor modulates to coil leaving
air temperature setpoint (adjustable). This continues until
(return) room air temperature is satisfied.
Dx Cooling, WSHP Cooling, Two Compressors
or Two-stage Single Compressor (Room Air
Temperature Control)
If the outside air temperature is above the summer set-
point (selectable) and if the (return) room air temperature
rises above the summer zone setpoint and the coil leaving
air is above the coil leaving setpoint, the first compressor
starts. If more cooling is needed, based on the coil leav-