Controls Data
Sequence Of Operation
Before start-up, check the unit for obstructive packaging,
objects near or in blowers, dampers, etc. Once installation is
complete, close the doors and check for correct unit operation
as described in the Ventilation Control section below.
Ventilation Control
Install the power to the unit as per local electrical codes and
complete the following ventilation control modes to ensure
proper unit operation.
Unoccupied Mode
With Or Without Ventilation Call
Occupied timer/sensor connection open (unoccupied mode).
Supply and exhaust fan motors are off.
Recirculation defrost damper (if equipped) closes off the
outside air opening.
External hood dampers (if equipped) are closed.
Occupied Mode
No Ventilation Call
Occupied timer/sensor connection closed (occupied mode).
Supply and exhaust fan motors are off.
Recirculation defrost damper (if equipped) closes off the
outside air opening.
External hood dampers (if equipped) are closed.
Ventilation Call
Occupied timer/sensor connection closed (occupied mode).
Recirculation defrost damper (if equipped) opens, allowing
outside air to enter the unit.
External hood dampers (if equipped) are open.
Low speed connection closed (wire across low to common);
supply and exhaust fan motors operate in low speed.
High speed connection closed (wire across high to common);
supply and exhaust fan motors operate in high speed.
NOTE: If unit is equipped with single speed motors, motors will
operate on a call for either low or high speed ventilation.
Fan Interlock Contact
When connecting an HRV to the existing ductwork system of
an air handler, typically the air handler should be running when-
ever the ventilator is running. To achieve this combination, there
is a set of open contacts (labeled "FF") on the microprocessor
board which close when the ventilator is running. Please refer
to the wiring schematic for the exact location of these contacts.
HRV Control Wiring
A low voltage remote terminal strip interface is provided on all
units to allow interconnection of field wired controls. Depending
on the unit configuration, the low voltage remote wiring terminal
strips are either located on the exterior of the unit or inside the
unit on the control box. All field installed low voltage wiring must
be Class II and connected according to local codes. Excluding
the Wall Control terminals, all terminals are 24 VAC or dry con-
tact control.
NOTE: Refer to unit installation and operations manual for field wiring
to terminal strips of optional accessories.
Terminal Connections
Wall Control (Optional)
Requires a 4-wire LVT 24 gauge (or equivalent); remote
wall control runs on 12 VDC.
Occupied (or Unoccupied) Timer/Sensor
Requires dry contact; considered the "master control" for
the unit.
Voltage - 24 VAC
Provides 24 VAC, 40 VA for powering of accessories or
field wiring devices.
Remote Fan Control (LOW, COMMON, HIGH)
Requires dry contact; contact closure across LOW-COM
terminals engage low speed fan operation; contact closure
across HIGH-COM terminals engage high speed fan (if
equipped).
Dirty Filter Indicator (Optional)
Terminals used for interconnection of dirty filter sensor and
light indicator (optional).
Unocc. Recirc Controls (Unoccupied Recirculation Contacts,
Recirculation Defrost Units Only)
Requires 24 VAC; places unit in recirculation ventilation
mode allowing recirculation of air during unoccupied mode.
Field Wired Terminals
Used for field connecting of field supplied controls.
CONTROL CONTACTS
CLASS 2 VOLTAGE
WALL CONTROL
BLACK
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
NOTE:
Connections are all dry contacts
except wall control, wheel alarm
contacts and 24 VAC power contacts.
Use of 24 VAC circuit requires
isolating contacts (ex. thermostat)
to prevent interconnection of
Class 2 outputs.
RED
OCCUPIED
TIMER/
SENSOR
FIELD WIRED
TERMINALS
AB
UNOCC.
RECIRC
CONTACTS
LOW
COMMON
HIGH
DIRTY
FILTER
INDICATOR
(1.5A-24 VAC)
(ERV UNITS)
WHEEL
ALARM
OPTION
(24 VAC)
(ERV UNITS)
ENTHALPY
(-) 24 VAC
(40 VA)
(+) 24 VAC
GREEN
YELLOW
(RECIRC UNITS)
Terminal Connections Diagram