Effectiveness Performance Data
HRV1200i - POLYPROPYLENE AND ALUMINUM CORES
Model Number: PHE500-13.1H-12S-0.11
Model Number: AHE500-13.1H-12S-0.14T
Type: Plate (Plate) Nominal Airflow: 200 (200) scfm
Pressure Drop: 0.22 (0.09) inches
Leakage Ratings
Pressure Purge Angle
Differential EATR OACF or Setting
Test 1: -5.00 (-3.00) inches 0% (0%) 1.00 (1.00) N/A (N/A)
Test 2: 0.00 (0.00) inches 0% (0%) 1.00 (1.00) N/A (N/A)
Test 3: 5.00 (3.00) inches 0% (0%) 1.00 (1.00) N/A (N/A)
Thermal Effectiveness Ratings at 0" Pressure Differential
Sensible Latent Total
100% Airflow Heating Condition: 64% (60%) 0% (0%) 42% (39%)
75% Airflow Heating Condition: 66% (66%) 0% (0%) 44% (43%)
100% Airflow Cooling Condition: 55% (54%) 0% (0%) 21% (21%)
75% Airflow Cooling Condition: 60% (59%) 0% (0%) 23% (23%)
Net Sensible Net Latent Net Total
100% Airflow Heating Condition: 64% (60%) 0% (0%) 42% (39%)
75% Airflow Heating Condition: 66% (66%) 0% (0%) 44% (43%)
100% Airflow Cooling Condition: 55% (54%) 0% (0%) 21% (21%)
75% Airflow Cooling Condition: 60% (59%) 0% (0%) 23% (23%)
400
10%
30%
50%
70%
Effectiveness
650 1000 1250 1400
189 307 472
Airflow (L/s)
590 661
Airflow (cfm)
Based on equal amounts of outdoor air and return air.
Total Effectiveness (Cooling)
Sensible Effectiveness (Heating)
Latent Effectiveness (Heating)
Ratings outside the scope of the
A
HRI Energy Recovery Ventilation Certification Program.
n/a
Energy recovery component is certified by
AHRI to AHRI Standard 1060. Actual
performance in packaged equipment may vary.
HRV1200I - HM CORE
Model Number: EPE5000-13H-12S-0.1
Type: Plate Nominal Airflow: 200 scfm
Pressure Drop: 0.28 inches
Leakage Ratings
Pressure Purge Angle
Differential EATR OACF or Setting
Test 1: -0.50 inches 2.0% 1.00 N/A
Test 2: 0.00 inches 0.5% 1.01 N/A
Test 3: 0.50 inches 0.0% 1.02 N/A
Thermal Effectiveness Ratings at 0" Pressure Differential
Sensible Latent Total
100% Airflow Heating Condition: 60% 50% 56%
75% Airflow Heating Condition: 65% 55% 61%
100% Airflow Cooling Condition: 60% 38% 47%
75% Airflow Cooling Condition: 65% 45% 53%
Net Sensible Net Latent Net Total
100% Airflow Heating Condition: 60% 50% 56%
75% Airflow Heating Condition: 65% 55% 61%
100% Airflow Cooling Condition: 60% 38% 47%
75% Airflow Cooling Condition: 65% 45% 53%
400
30%
50%
70%
90%
Effectiveness
600 800 1000 1200
94 165 236
Airflow (L/s)
307 378
Airflow (cfm)
Based on equal amounts of outdoor air and return air.
Total Effectiveness (Cooling)
Sensible Effectiveness (Heating)
Latent Effectiveness (Heating)
Ratings outside the scope of the
AHRI Energy Recovery Ventilation Certification Program.
Energy recovery component is certified by
AHRI to AHRI Standard 1060. Actual
performance in packaged equipment may vary.